Type: FR-A800-R2R (FOR ROLL TO ROLL)
Series: FR-A800 PLUS SERIES
Serial Number: 412458
Product Details: InverterAC without DC Choke;Pn:90-160kW;3×380-500V;In max:325A;(110kW; 216A)IP00
INVERTER
SERIES FR-A800 PLUS SERIES
TYPE FR-A800-R2R (FOR ROLL TO ROLL)
MINIMUM RATED VOLTAGE (V) 380
MIN. PERMISSIBLE VOLTAGE (V) 323
MAXIMUM RATED VOLTAGE (V) 500
MAX. PERMISSIBLE VOLTAGE (V) 550
CURRENT TYPE AC
PHASES 3
RATED OUTPUT CURRENT SLD (A) 325
RATED OUTPUT CURRENT LD (A) 260
RATED OUTPUT CURRENT ND (A) 216
RATED OUTPUT CURRENT HD (A) 180
RATED MOTOR CAPACITY SLD (KW) 160
RATED MOTOR CAPACITY LD (KW) 132
RATED MOTOR CAPACITY ND (KW) 110
RATED MOTOR CAPACITY HD (KW) 90
CONTROL METHOD SOFT-PWM/HIGH FRQ PWM/VECTOR
MOTOR TYPE INDUCTION MOTOR
INTEGRATED EMC FILTER YES
SAFE TORQUE OFF (STO) YES
REGENERATIVE (4Q) NO
INTEGRATED DC CHOKE NO
DISPLAY FR-DU08
DISPLAY TYPE 5 DIGITS LED
PLC FUNCTION YES
PROGRAM MEMORY 6K
PROGRAM MEMORY UNIT STEPS
INTEGRATED DIGITAL INPUTS 12
DIGITAL OUTPUTS (TRANSISTOR) 5
DIGITAL OUTPUTS (RELAY) 2
INTEGRATED ANALOGUE INPUTS 3
INTEGRATED ANALOGUE OUTPUTS 2
TYPE OF TERMINAL BLOCK PLUG
EXPANDABLE YES
USB 2
BUILT-IN NETWORK MODBUS-RTU
PROTECTION CLASS IP20
STANDBY POWER CONSUMPTION (W) 75
LEAKAGE CURRENT (MA) 35(DELTA) / 2(STAR)
ETHERNET PORT 1
POWER LOSS SLD (W) 3600
POWER LOSS LD (W) 2800
POWER LOSS ND (W) 2300
POWER LOSS HD (W) 1850
ADDITIONAL PRODUCT INFORMATION
DIFFERENCE TO STANDARD 1 ROLL TO ROLL CONTROL
PRODUCT DIMENSIONS & WEIGHT
WIDTH (MM) 465
HEIGHT (MM) 740
DEPTH (MM) 360
WEIGHT (KG) 71