Type: FR-D700 COMPACT INVERTER
Series: FR-D700 SERIES
Serial Number: 217400
Product Details: Description
Variable Speed/Frequency Drive (VSD/VFD) / Inverter – Mitsubishi Electric (FREQROL FR-D700 series) – input voltage 200Vac-240Vac (208Vac / 220Vac / 230Vac) (3-phase / 3P) – Rated active power 200W / 0.2kW / 1/4HP – Rated current 1.4A – frequency (output) 0.2-400Hz – with Heatsnk. cooling – with Modbus RTU communication capability – IP20
Specifications
Primary brandMitsubishi Electric
Main functionVariable Speed/Frequency Drive (VSD/VFD) / Inverter
Product series / family nameFREQROL FR-D700 series
Supply voltage (AC)200Vac-240Vac (208Vac / 220Vac / 230Vac)
FunctionsVariable Speed/Frequency Drive (VSD/VFD) / Inverter
Soft-PWM control
High carrier frequency PWM control
Maximum/minimum frequency setting
Frequency jump operation
External thermal relay input selection
Automatic restart after instantaneous power failure operation
Forward/reverse rotation prevention
Remote setting
Second function
Multi-speed operation
Regeneration avoidance
Slip compensation
Operation mode selection
Offline auto tuning function
PID control
Computer link operation (RS-485)
Optimum excitation control
Power failure stop
Speed smoothing control
DesignHeatsnk. cooling
Rated current1.4A
150% In for 60s / 200% In for 0.5s overload current rating (inverse-time characteristics)
Rated active power (kW)200W / 0.2kW
Rated power (HP)1/4HP
Communication protocolModbus RTU
Digital inputs1 x digital input (source/sink) (STF)
1 x digital input (source/sink) (STR)
1 x digital input (source/sink) (RH)
1 x digital input (source/sink) (RM)
1 x digital input (source/sink) (RL)
1 x digital input (safe stop channel 1)
1 x digital input (safe stop channel 2)
Digital outputs1 x digital output (SPDT (Single Pole Double Throw contact A/B/C) (programmable)
1 x digital output (open collector transistor) (programmable)
1 x digital output (PTO Pulse Train Output for indicator)
1 x digital output (programmable) (SO – Safety Monitor Output)
Analog inputs1 x analog input (0-5Vdc / 0-10Vdc)
1 x analog input (0-5Vdc / 0-10Vdc / 4-20mA)
Degree of protectionIP20
Protection functionsOvercurrent during acceleration
overcurrent during constant speed
overcurrent during deceleration
overvoltage during acceleration
overvoltage during constant speed
overvoltage during deceleration
inverter protection thermal operation
motor protection thermal operation
Hheatsink overheat
output short circuit
parameter error
PU disconnection
CPU fault
brake transistor alarm
inrush resistance overheat
analog input error
stall prevention operation
Safety circuit fault
Output phase loss
Output side earth (ground) fault overcurrent at start
External thermal relay operation
PTC thermistor operation
Retry count excess
output current detection value exceeded
Input phase loss
Compliant with standard(s)EN ISO 13849-1 Category 3
EN62061
IEC61508 SIL2 PLd
Equivalent toFRD72002K
Rated apparent power (S)0.6kVA
Type of network3-phase / 3P
Application typeTransfer
Lift
Packaging
Machine tool
Air conditioning
Fan
Pump
Network frequency(output) 0.2-400 Hz